858.458.0223
179
BPS Series : Specications
30–180 kVA
AC Input
Voltage Must be specied at time of order. All inputs are L-L, 3ø, 3 wire + Gnd. 208 ± 10% VAC, 230 ± 10% VAC, 400 ± 10% VAC,
480 ± 10% VAC
Input Line Current (per phase)
BPS30-1/3 BPS45-1/3 BPS75 BPS90 BPS150 BPS180
116 ARMS @ 187 VLL
105 ARMS @ 207 VLL
60 ARMS @ 360 VLL
50 ARMS @ 432 VLL
175 ARMS @ 187 VLL
157 ARMS @ 207 VLL
90 ARMS @ 360 VLL
75 ARMS @ 432 VLL
285 ARMS @187 VLL
256 ARMS @ 207 VLL
147 ARMS @ 360 VLL
122 ARMS @ 432 VLL
350 ARMS @ 187 VLL
314 ARMS @ 207 VLL
180 ARMS @ 360 VLL
150 ARMS @ 432 VLL
Each BPS75 chassis
requires its own AC
service. Total Line
currents are 2 x
BPS75
Each BPS90 chassis
requires its own AC
service. Total Line
currents are 2 x
BPS90
Line Frequency 47 - 63 Hz
Efciency 85 % typical
Power Factor 0.95 typical
AC Service
Inputs/Outputs Rear panel connection
Regulatory IEC61010, EN50081-2, EN50082-2, CE EMC and Safety Mark requirements
EMI CISPR 11, Group1 , Class A
Connectors All remote interface connections available from the rear panel.
Measurement
Measurements - Standard
(AC Measurements)
Parameter Frequency RMS
Voltage
RMS
Current
Peak
Current
Crest
Factor
Real
Power
Apparent
Power
Power
Factor
Phase
Range 16-100 Hz
100-820 Hz
0-400 V 0-300 A 0-800 A 0.00-6.00 90 kW 90 kW 0.00-1.00 0.0-360.0
Accuracy*
(±)
0.01% + 0.01 Hz 0.05 V + 0.02%
0.1 V + 0.02%
0.15 A + .02%
0.3 A + .02%
0.15 A + 0.02%
0.3 A + .02%
0.05
0.05
30 W + 0.1%
60 W + 0.1%
30 VA + 0.1%
60 VA + 0.1%
0.01
0.02
2.0°
3.0°
Resolution* 0.01 Hz /
0.1 Hz
10 mV 10 mA 10 mA 0.01 10 W 10 VA 0.01 0.1°
* Measurement system bandwidth = DC to 6.7 kHz. Accuracy specications are valid above 100 counts. Current and Power Accuracy and Range specications are times
three for BPS 150 and BPS180 in single phase mode. PF accuracy applies for PF > 0.5 and VA > 50 % of range
Protection
Over Load Constant Current or Constant Voltage mode
Over Temperature Automatic shutdown
Storage
Non Volatile Mem. storage 16 instrument setups, 200 user dened waveforms [Pi only]
Waveforms
Waveform Types Std: Sine Wave
System Interface
Inputs Remote shutdown
Outputs Function Strobe / Trigger out
Remote Control
IEEE-488 Interface IEEE-488 (GPIB) talker listener. Subset: AH1, C0, DC1, DT1, L3, PP0, RL2, SH1, SR1, T6, IEEE-488.2 SCPI Syntax
RS232C Interface 9 pin D-shell connector (Supplied with RS232C cable)
LAN ( option ) Ethernet Interface: 10BaseT, 100BaseT, RJ45
USB Version: USB 1.1; Speed: 460 Kb/s maximum
Output Relay Push button controlled or bus controlled output relay
Physical Dimensions
BPS30/45 Dimensions Height: 50” 1270 mm, Width: 28.75” 731mm, Depth: 34.5” 876mm
BPS30/45 Weight Per Chassis: Net: 1150 lbs / 522 Kg approximately, Shipping: 1231 lbs / 560 Kg approximately
BPS75/90 Dimensions Height: 76” 1930 mm, Width: 32.0” 812mm, Depth: 40.0” 1016mm
BPS75/90 Weight Per Chassis: Net: 1650 lbs / 748 Kg approximately, Shipping: 1731 lbs / 785 Kg approximately
Chassis Casters and forklift openings.
Vibration and Shock Designed to meet NSTA project 1A transportation levels. Units are shipped in wooden crate with forklift slots
Air Intake/Exhaust Forced air cooling, front air intake, rear exhaust
Operating Humidity 0 to 95 % RAH, non condensing
Temperature Operating: 0 to 40° C (30° C max in CP mode), Storage: -20 to +85° C