858.458.0223
179
BPS Series : Specications
30–180 kVA
AC Input
Voltage Must be specied at time of order. All inputs are L-L, 3ø, 3 wire + Gnd. 208 ± 10% VAC, 230 ± 10% VAC, 400 ± 10% VAC,
480 ± 10% VAC
Input Line Current (per phase)
BPS30-1/3 BPS45-1/3 BPS75 BPS90 BPS150 BPS180
116 ARMS @ 187 VLL
105 ARMS @ 207 VLL
60 ARMS @ 360 VLL
50 ARMS @ 432 VLL
175 ARMS @ 187 VLL
157 ARMS @ 207 VLL
90 ARMS @ 360 VLL
75 ARMS @ 432 VLL
285 ARMS @187 VLL
256 ARMS @ 207 VLL
147 ARMS @ 360 VLL
122 ARMS @ 432 VLL
350 ARMS @ 187 VLL
314 ARMS @ 207 VLL
180 ARMS @ 360 VLL
150 ARMS @ 432 VLL
Each BPS75 chassis
requires its own AC
service. Total Line
currents are 2 x
BPS75
Each BPS90 chassis
requires its own AC
service. Total Line
currents are 2 x
BPS90
Line Frequency 47 - 63 Hz
Efciency 85 % typical
Power Factor 0.95 typical
AC Service
Inputs/Outputs Rear panel connection
Regulatory IEC61010, EN50081-2, EN50082-2, CE EMC and Safety Mark requirements
EMI CISPR 11, Group1 , Class A
Connectors All remote interface connections available from the rear panel.
Measurement
Measurements - Standard
(AC Measurements)
Parameter Frequency RMS
Voltage
RMS
Current
Peak
Current
Crest
Factor
Real
Power
Apparent
Power
Power
Factor
Phase
Range 16-100 Hz
100-820 Hz
0-400 V 0-300 A 0-800 A 0.00-6.00 90 kW 90 kW 0.00-1.00 0.0-360.0
Accuracy*
(±)
0.01% + 0.01 Hz 0.05 V + 0.02%
0.1 V + 0.02%
0.15 A + .02%
0.3 A + .02%
0.15 A + 0.02%
0.3 A + .02%
0.05
0.05
30 W + 0.1%
60 W + 0.1%
30 VA + 0.1%
60 VA + 0.1%
0.01
0.02
2.0°
3.0°
Resolution* 0.01 Hz /
0.1 Hz
10 mV 10 mA 10 mA 0.01 10 W 10 VA 0.01 0.1°
* Measurement system bandwidth = DC to 6.7 kHz. Accuracy specications are valid above 100 counts. Current and Power Accuracy and Range specications are times
three for BPS 150 and BPS180 in single phase mode. PF accuracy applies for PF > 0.5 and VA > 50 % of range
Protection
Over Load Constant Current or Constant Voltage mode
Over Temperature Automatic shutdown
Storage
Non Volatile Mem. storage 16 instrument setups, 200 user dened waveforms [Pi only]
Waveforms
Waveform Types Std: Sine Wave
System Interface
Inputs Remote shutdown
Outputs Function Strobe / Trigger out
Remote Control
IEEE-488 Interface IEEE-488 (GPIB) talker listener. Subset: AH1, C0, DC1, DT1, L3, PP0, RL2, SH1, SR1, T6, IEEE-488.2 SCPI Syntax
RS232C Interface 9 pin D-shell connector (Supplied with RS232C cable)
LAN ( option ) Ethernet Interface: 10BaseT, 100BaseT, RJ45
USB Version: USB 1.1; Speed: 460 Kb/s maximum
Output Relay Push button controlled or bus controlled output relay
Physical Dimensions
BPS30/45 Dimensions Height: 50” 1270 mm, Width: 28.75” 731mm, Depth: 34.5” 876mm
BPS30/45 Weight Per Chassis: Net: 1150 lbs / 522 Kg approximately, Shipping: 1231 lbs / 560 Kg approximately
BPS75/90 Dimensions Height: 76” 1930 mm, Width: 32.0” 812mm, Depth: 40.0” 1016mm
BPS75/90 Weight Per Chassis: Net: 1650 lbs / 748 Kg approximately, Shipping: 1731 lbs / 785 Kg approximately
Chassis Casters and forklift openings.
Vibration and Shock Designed to meet NSTA project 1A transportation levels. Units are shipped in wooden crate with forklift slots
Air Intake/Exhaust Forced air cooling, front air intake, rear exhaust
Operating Humidity 0 to 95 % RAH, non condensing
Temperature Operating: 0 to 40° C (30° C max in CP mode), Storage: -20 to +85° C
Vue de la page 4