Antec Solution 1650B User's Manuel d'utilisateur Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 6
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
www.ProgrammablePower.com178
Operating Modes
BPS Series AC
AC Mode Output
Frequency Range: 16.00-819.0 Hz, -LF Option: 16.00-500.0 Hz,
Resolution: 0.01 Hz: 16.00 - 81.91 Hz, 0.1 Hz: 82.0 Hz - 819.1 Hz
Phase Outputs 1 or 3 Neutral: Floating, Coupling: DC (except for -HV option) Please specify Single (-1) or Three Phase (-3) for BPS30 and BPS45
at time of order.
Total Power BPS30-1/3; 30kVA, BPS45-1/3: 45kVA, BPS75-3: 75kVA, BPS90-3: 90kVA, BPS150-3:150kVA, BPS180-3, 180kVA
Load Power Factor 0 to unity at full output current
AC Mode Voltage
Voltage Ranges
Range V Low V High Load Regulation < 0.25 % FS to 100 Hz, < 0.5 % FS 100 Hz to 819 Hz
AC 0-150 V 0-300 V Line Regulation < 0.1% FS for 10 % line change
External Sense Voltage drop compensation (5% Full Scale)
Harmonic Distortion (Linear) Less than 0.5% from 16 - 66 Hz, Less than 1% from 66 - 500 Hz, Less than 1.25% above 500 Hz
DC Offset < 20 mV
Load Regulation 0.25% FS @ - 100 Hz, 0.5% FS > 100 Hz
External Amplitude Modulation Depth: 0 - 10 %, Frequency: DC - 2 KHz
Voltage slew rate 200 µs for 10% to 90% of full scale change into resistive load, 0.5V / µSec
AC Mode Current
Output
Model BPS30-1/3 BPS45-1/3 BPS75 BPS90 BPS150 BPS180
30 KVA 45 KVA 75 KVA 90 KVA 150 KVA 180 kVA
BPS30-1
V Lo:200 A
V Hi: 100A
Single phase
BPS30-3
V Lo: 66.7A
V Hi: 33.3A
per phase 3 phase
BPS45-1
V Lo:300 A
V Hi: 150A
Single phase
BPS45-3
V Lo: 100
V Hi: 50A
per phase 3 phase
BPS75
V Lo: 166A
V Hi: 83A per
phase
BPS90
V Lo:200A
V Hi: 100A per
phase
BPS150
V Lo:332A
V Hi: 166A per
phase
BPS180
V Lo:400A
V Hi: 200A per
phase
Note: Constant power mode provides increased current at reduced voltage. See chart below
Peak Repetitive AC Current 4.5 x RMS current for BPS30, 3.0 x RMS current for BPS45, 3.6 x RMS current for BPS75 and 3.0 x RMS current for BPS90.
BPS150 is 2x BPS75 and BPS180 is 2x BPS90
Programming Accuracy Voltage (rms): ± 0.3 Vrms, Frequency: ± 0.01 % of programmed value, Current Limit: - 0 % to + 5 % of programmed value + 1A, Phase:
< 0.5° + 0.2°/ 100 Hz with balanced load
Programming Resolution Voltage (rms): 100 mV, Frequency: 0.01 Hz from 16 - 81.91 Hz, 0.1 Hz from 82.0 - 819 Hz, Current Limit: 0.1 A, 3 phase mode,
1.0 A, 1 phase mode, Phase: 0.1°
Constant Power AC Mode - Available Max. AC Current
Current
(RMS)
Voltage (RMS)
Full
Power
125%
100%
20%
50%
10% 80%
50%
100%
Note: Specications are subject to change without notice. Specications are warranted over an ambient temperature range of 25°± 5° C. Unless otherwise noted, specications are per phase
for a sinewave with a resistive load and apply after a 30 minute warm-up period. For three phase congurations, all specications are for L-N. Phase angle specications are valid under
balanced load conditions only.
BPS Series : Specications
© 2009 AMETEK Programmable Power All rights reserved. AMETEK Programmable Power is the trademark of AMETEK Inc., registered in the U.S. and other countries. Elgar, Sorensen,
California Instruments, and Power Ten are trademarks of AMETEK Inc., registered in the U.S.
Vue de la page 3
1 2 3 4 5 6

Commentaires sur ces manuels

Pas de commentaire